15-18 Setting Control Output as Open or Closed
LX Series Configuration Guide
Setting Control Output as Open or Closed
Use the following commands to set LX-7204T/7304T Control
Output signals as Open or Closed for a specific control or for
multiple controls.
X To configure control output name as open or closed for
a specific control
Use the following command syntax:
Syntax hdam control <control_name> set [open|closed]
X To configure control output name as open or closed for
multiple controls
Use the following command syntax:
Syntax hdam control port <port_number> slot [<slot_list>|all]
point [<
point_list>|all] set [open|closed]
where
Example
port_number The number of the port to which the HDAM is connected.
control_name Specifies a Control Output Name. The default name for
an alarm input or control output is canonically derived
from the port number, slot number and point number.
For example, the default name for the 8th control output
on the 2
nd
slot of the HDAM being managed by port 1 is 1_
2_8.
slot_list The list of the slots whose points to configure as open or
closed. The list can contain single items (such as 1,3,4) or
ranges (such as 1-4), or a combination.
point_list The list of the points whose state to set open or closed.
The list can contain single items (such as 1,3,4) or ranges
(such as 1-8), or a combination.
open|closed Set the specified Control Output signals to Open|Closed.
Closed is the default setting.
Config:0 >>hdam control 5_4_8 set open
Config:0 >>hdam control 3_1_8 set closed
Config:0 >>hdam control port 2 slot all point 1-4 set open